1、 總則
1.1 為提高高壓開(kai)關設備(以下(xia)(xia)簡稱開(kai)關設備)的(de)運行可靠性,根據事(shi)故分析(xi)和(he)各地區(qu),各部門的(de)經驗,提出以下(xia)(xia)反(fan)事(shi)故技術措施(shi)(shi),國家電力公司系(xi)統各有關設計,基(ji)建,安(an)裝,運行,檢修和(he)試驗單位(wei)均(jun)應認真(zhen)執行.各運行單位(wei)亦應結合(he)(he)本(ben)地區(qu)具體情況和(he)經驗,制(zhi)訂(ding)適合(he)(he)本(ben)地區(qu)的(de)補充反(fan)事(shi)故技術措施(shi)(shi).
1.2 為(wei)保證開(kai)關(guan)設(she)(she)備(bei)(bei)(bei)安全運行(xing),必須建立和(he)健(jian)全管理體系,加強開(kai)關(guan)設(she)(she)備(bei)(bei)(bei)的技術(shu)管理工作,各單(dan)位均應認真貫徹(che)和(he)執(zhi)行(xing)國家(jia)電力公(gong)司頒布的《高(gao)壓開(kai)關(guan)設(she)(she)備(bei)(bei)(bei)管理規定》和(he)《高(gao)壓開(kai)關(guan)設(she)(she)備(bei)(bei)(bei)質(zhi)量監督(du)管理辦法》的各項條款.
1.3 各(ge)級電力公司要加強對(dui)開(kai)關設備(bei)安(an)裝,運行,檢修和試驗(yan)人員的技(ji)(ji)術(shu)培訓工(gong)作,使之(zhi)熟悉和掌握所轄范圍(wei)內開(kai)關設備(bei)結構性(xing)能及安(an)裝,運行,檢修和試驗(yan)的技(ji)(ji)術(shu)要求(qiu).
2 、選用高壓開關設(she)備技術措施
2.1 凡不符合國家(jia)電力公(gong)司《高壓開關設備(bei)質量監督(du)管理辦法》,國家(jia)(含原機械,電力兩部)已明令停(ting)止生(sheng)產,使用的各種型號(hao)開關設備(bei),一(yi)律(lv)不得選(xuan)用.
2.2 凡新建變電(dian)所的高(gao)壓(ya)斷路器,不得再選用手力(li)操動機(ji)構.對正在運行的高(gao)壓(ya)斷路器手力(li)操動機(ji)構要盡快更換,以操作人(ren)員的人(ren)身安(an)全(quan).
2.3 中性點(dian)不(bu)接地(di),小電(dian)流接地(di)及二線一地(di)制系統(tong)應選用異相接地(di)開斷(duan)試驗合格的開關設(she)備.
2.4 切合(he)電(dian)(dian)容器組應(ying)選(xuan)用開(kai)斷電(dian)(dian)容電(dian)(dian)流無重擊穿及(ji)適合(he)于頻(pin)繁操作(zuo)的斷路器.
2.5 對電纜線路和35kV及以上(shang)電壓等級架空線路,應選用切合時無重擊(ji)穿的斷路器.
2.6 用于切合(he)110kV及以上電(dian)壓(ya)等級變(bian)壓(ya)器的(de)斷(duan)路(lu)器,其過電(dian)壓(ya)不應超過2.5~2.0倍(bei).
2.7 對(dui)于(yu)頻繁啟停的(de)高(gao)壓感應電(dian)機回路應選(xuan)用SF6斷路器(qi)或(huo)真空(kong)斷路器(qi),接觸器(qi)等(deng)開關設(she)備,其過(guo)電(dian)壓倍數應滿足感應電(dian)機絕緣水(shui)平的(de)要求,同時(shi)應采取過(guo)電(dian)壓保護措施.
3、 新裝(zhuang)和(he)檢修(xiu)高(gao)壓開關設備技術措施(shi)
3.1 設備的交接驗收(shou)必須嚴格按照國家,電力行業和國家電力公司標準,產品技術條件及合同書的技術要求進行.不符合交接驗收(shou)條件不能驗收(shou)投運.
3.2 新裝及檢(jian)(jian)修后(hou)的(de)開關(guan)設(she)備必須(xu)嚴格按照《電(dian)氣裝置安裝工程電(dian)氣設(she)備交接試驗(yan)標準》,《電(dian)力設(she)備預防性試驗(yan)規程》,產品技(ji)術條件及原部頒有關(guan)檢(jian)(jian)修工藝異則的(de)要求進(jin)行(xing)試驗(yan)與檢(jian)(jian)查.交接時對重(zhong)要的(de)技(ji)術指標一定要進(jin)行(xing)復查,不(bu)合格者不(bu)準投運.
3.3 分,合閘速(su)度特性(xing)(xing)是檢修調試斷路(lu)器(qi)的(de)重要(yao)質量指標(biao),也是直接影響開(kai)斷和(he)關(guan)合性(xing)(xing)能的(de)關(guan)鍵技術(shu)(shu)數據.各種斷路(lu)器(qi)在(zai)新裝(zhuang)和(he)大(da)修后必(bi)須測量分,合閘速(su)度特性(xing)(xing),并應(ying)符(fu)合技術(shu)(shu)要(yao)求.SF6產品的(de)機(ji)構檢修參照少油斷路(lu)器(qi)機(ji)構檢修工(gong)藝進(jin)行,運(yun)行5年(nian)左右應(ying)進(jin)行一(yi)次機(ji)械特性(xing)(xing)檢查.
3.4 新裝(zhuang)及(ji)大修后的(de)(de)252kV及(ji)以上電(dian)壓等級斷路器,其(qi)相(xiang)間不同期及(ji)同相(xiang)各(ge)斷口間的(de)(de)不同期,必須用(yong)精度滿足要求(qiu)的(de)(de)儀(yi)器進行測量,并應符合(he)產品技術要求(qiu).現場不能測量的(de)(de)參(can)數(shu),制造廠應提(ti)供必要的(de)(de)保證.
3.5 新裝(zhuang)(zhuang)的(de)國(guo)(guo)產油開關(guan)設備(bei),安(an)裝(zhuang)(zhuang)前(qian)應解(jie)體(ti).國(guo)(guo)產SF6開關(guan),液壓機構(gou)和(he)氣動機構(gou)原則(ze)上(shang)應解(jie)體(ti).若制造廠承諾可(ke)不(bu)解(jie)體(ti)安(an)裝(zhuang)(zhuang),則(ze)可(ke)不(bu)解(jie)體(ti)安(an)裝(zhuang)(zhuang).由于不(bu)解(jie)體(ti)安(an)裝(zhuang)(zhuang)發生(sheng)設備(bei)質量事故造成的(de)經濟損失由制造廠承擔(dan).
4、 預防斷路器滅弧室燒損,爆炸
4.1 各(ge)運行(xing),維修單(dan)位應(ying)根據可能出現的系統運行(xing)方式(shi)(shi)及可能采用的各(ge)種運行(xing)方式(shi)(shi),每年定期核算開關設備安(an)裝地(di)點的短(duan)路電流(liu).如開關設備實際短(duan)路開斷電流(liu)不(bu)能滿足要求,則應(ying)采取"限制,調(diao)整,改造(zao),更換(huan)"的辦法,以設備安(an)全運行(xing).具體措施如下:
(1)合理(li)改(gai)變(bian)系(xi)統(tong)運行方式,限(xian)制和減少系(xi)統(tong)短路電流.
(2)采取限(xian)(xian)流(liu)措施,如加裝電抗器(qi)等以(yi)限(xian)(xian)制(zhi)短路(lu)電流(liu).
(3)在繼(ji)電保護上采取相應的措施,如控制斷路器的跳閘順序等.
(4)將短路開斷(duan)(duan)電(dian)流小的斷(duan)(duan)路器調換到短路電(dian)流小的變電(dian)所.(5)根據具(ju)體情況,更換成短路開斷(duan)(duan)電(dian)流大的斷(duan)(duan)路器.
4.2 應經常注意監視油(you)(you)(you)斷路器滅弧(hu)室的油(you)(you)(you)位,發(fa)現油(you)(you)(you)位過低或滲漏油(you)(you)(you)時應及時處理(li),嚴禁在嚴重缺油(you)(you)(you)情(qing)況下運(yun)行(xing).油(you)(you)(you)斷路器發(fa)生開斷故障(zhang)后,應檢查其(qi)噴(pen)油(you)(you)(you)及油(you)(you)(you)位變(bian)化情(qing)況,發(fa)現噴(pen)油(you)(you)(you)嚴重時,應查明原因(yin)并及時處理(li).
4.3 開(kai)(kai)(kai)關(guan)設備應按規(gui)定(ding)的(de)檢(jian)修(xiu)周期和具體短路開(kai)(kai)(kai)斷(duan)次(ci)數(shu)及狀態進行(xing)檢(jian)修(xiu),做到"應修(xiu)必修(xiu),修(xiu)必修(xiu)好(hao)".不經檢(jian)修(xiu)的(de)累(lei)計(ji)短路開(kai)(kai)(kai)斷(duan)次(ci)數(shu),按斷(duan)路器技(ji)術條件規(gui)定(ding)的(de)累(lei)計(ji)短路開(kai)(kai)(kai)斷(duan)電流或檢(jian)修(xiu)工(gong)藝執行(xing).沒(mei)有規(gui)定(ding)的(de),則可(ke)根據現場運(yun)(yun)行(xing),檢(jian)修(xiu)經驗由各(ge)運(yun)(yun)行(xing)單位的(de)總(zong)工(gong)程師參照類似開(kai)(kai)(kai)關(guan)設備檢(jian)修(xiu)工(gong)藝確定(ding).
4.4 當斷路器所配液壓(ya)機構打壓(ya)頻繁或突然失壓(ya)時應申請停電處理.必須帶(dai)電處理時,檢修人(ren)員在未(wei)采取可(ke)靠防慢(man)分措施(如加裝機械卡具)前,嚴禁人(ren)為啟動油泵,防止由于慢(man)分而(er)使(shi)滅弧室(shi)爆(bao)炸.
|<1234>>
5、 預防(fang)套管,支持絕(jue)緣子和絕(jue)緣提(ti)升(sheng)桿閃絡,爆炸(zha)
5.1 根據設備運(yun)行(xing)現場的(de)污穢程度,采取下列防污閃措施(shi):
(1)定期對瓷(ci)套(tao)或(huo)支持絕緣子進行清洗(xi).
(2)在室外40.5kV及以(yi)上電壓等級開關設備的瓷套或支持絕緣子上涂PTV硅有機涂料或采(cai)用合成增(zeng)爬裙.
(3)采用加強外(wai)絕緣爬距的(de)瓷套或(huo)支持絕緣子.
(4)采取措(cuo)施防止開(kai)關設備瓷套滲漏油,漏氣(qi)及進水.
(5)新裝投運(yun)的開關設備(bei)必(bi)須(xu)符合防污等級要求.
5.2 加強(qiang)對套管和支持絕緣子內部(bu)絕緣的(de)檢查.為預防(fang)因內部(bu)進水使絕緣降低,除進行定(ding)期(qi)的(de)預防(fang)性試驗外,在(zai)雨(yu)季應(ying)加強(qiang)對絕緣油(you)的(de)絕緣監視.
5.3 新裝(zhuang)725kV及(ji)以上電壓(ya)(ya)等級斷路(lu)器的(de)絕緣拉桿,在安裝(zhuang)前必(bi)(bi)須(xu)進(jin)行(xing)(xing)外觀檢查,不(bu)得有開裂起皺,接頭松動(dong)及(ji)超過允(yun)許限(xian)度的(de)變形.除進(jin)行(xing)(xing)泄漏(lou)試驗(yan)外,必(bi)(bi)要時應進(jin)行(xing)(xing)工頻耐(nai)壓(ya)(ya)試驗(yan).運行(xing)(xing)的(de)斷路(lu)器如(ru)發現絕緣拉桿受潮,烘(hong)干(gan)處理完畢(bi)后(hou),也要進(jin)行(xing)(xing)泄漏(lou)和工頻耐(nai)壓(ya)(ya)試驗(yan),不(bu)合(he)格(ge)者應予更換.
5.4 充膠(油(you)(you))電(dian)容(rong)套(tao)管應采取有效措(cuo)施防止進(jin)水和(he)受(shou)潮,發現(xian)膠質溢出,開裂,漏油(you)(you)或油(you)(you)箱內油(you)(you)質變黑(hei)時應及時進(jin)行處理或更換.大修時應檢查(cha)電(dian)容(rong)套(tao)管的芯子有無松動現(xian)象,防止脫膠.
5.5 絕緣套管和支持絕緣子(zi)各(ge)連接部(bu)位(wei)的橡膠密(mi)封圈應采用合格(ge)品(pin)并(bing)(bing)妥善保管.安裝時應無變(bian)形(xing)(xing),位(wei)移,龜(gui)裂(lie),老化或(huo)損(sun)壞(huai).壓(ya)緊時應均(jun)勻用力(li)并(bing)(bing)使其有一定的壓(ya)縮量(liang).避免因用力(li)不(bu)均(jun)或(huo)壓(ya)縮量(liang)過大而使其永久(jiu)變(bian)形(xing)(xing)或(huo)損(sun)壞(huai).
6 、預防斷路器(qi)拒分,拒合和誤動等操(cao)作(zuo)故障
6.1 加(jia)強(qiang)對操動(dong)機(ji)構(gou)的維護檢查.機(ji)構(gou)箱門應(ying)關閉嚴密(mi),箱體(ti)應(ying)防水,防灰塵和(he)小動(dong)物(wu)進入,并保持內(nei)部干燥清潔(jie).機(ji)構(gou)箱應(ying)有通(tong)風和(he)防潮(chao)措施(shi),以防線圈,端子排等受潮(chao),凝露,生銹.液(ye)壓(ya)機(ji)構(gou)箱應(ying)有隔熱防寒措施(shi).
6.2 輔助(zhu)開關(guan)應采取(qu)下(xia)列措(cuo)施:
(1)輔(fu)助(zhu)開關(guan)應安裝牢(lao)固,防止因多次操作松動變位(wei).
(2)應(ying)保證輔助(zhu)開(kai)關(guan)接點轉(zhuan)換(huan)靈(ling)活,切換(huan)可靠(kao),接觸良好,性能穩定,不符合要求時應(ying)及時調整或更(geng)換(huan).
(3)輔助(zhu)開關(guan)和機構間(jian)的(de)連接應松緊(jin)適當,轉(zhuan)換(huan)靈活,并滿足通電時間(jian)的(de)要求.連桿鎖緊(jin)螺帽應擰緊(jin),并采(cai)用(yong)防松措(cuo)施(shi),如涂厭氧膠等.
6.3 斷路器操(cao)動機構(gou)檢(jian)修后,應檢(jian)查操(cao)動機構(gou)脫扣器的動作(zuo)電壓是否(fou)符(fu)合(he)30%和65%額(e)定操(cao)作(zuo)電壓的要求(qiu).在80%(或85%)額(e)定操(cao)作(zuo)電壓下,合(he)閘(zha)接觸(chu)器是否(fou)動作(zuo)靈活(huo)且吸持(chi)牢靠.
6.4 分,合閘鐵芯應動作靈活(huo),無(wu)卡澀現象,以(yi)防(fang)拒(ju)(ju)分或(huo)拒(ju)(ju)合.
6.5 斷路器大修時應檢查液壓機構分(fen),合(he)閘閥的頂針是否(fou)松動或變形.
6.6 長期(qi)處于(yu)備用狀態(tai)的斷路器應定期(qi)進行(xing)分,合操(cao)作檢(jian)查.在低溫(wen)地區還應采取防(fang)寒措施和進行(xing)低溫(wen)下的操(cao)作試(shi)驗.
6.7 氣動機構應堅(jian)持定期放(fang)水制(zhi)度.對于(yu)單機供氣的(de)氣動機構在冬(dong)季或低(di)溫季節應采取保溫措施,防(fang)止因控制(zhi)閥結冰而拒動.氣動機構各運動部位應保持潤(run)滑.
7 、預防直(zhi)流操作(zuo)電源故障引起斷(duan)路器拒動,燒損
34>>
7.1 各種直流(liu)(liu)操作電(dian)源均(jun)應(ying)保(bao)證斷路器合(he)(he)閘電(dian)磁鐵線(xian)圈通電(dian)時的(de)端(duan)子(zi)電(dian)壓不(bu)(bu)是低(di)于(yu)(yu)標(biao)準(zhun)要求.對電(dian)磁操動機構(gou)合(he)(he)閘線(xian)圈端(duan)子(zi)電(dian)壓,當(dang)關(guan)合(he)(he)電(dian)流(liu)(liu)小于(yu)(yu)50kA(峰值)時不(bu)(bu)低(di)于(yu)(yu)額(e)(e)定操作電(dian)壓的(de)80%;當(dang)關(guan)合(he)(he)電(dian)流(liu)(liu)等于(yu)(yu)或大于(yu)(yu)50kA(峰值)時不(bu)(bu)低(di)于(yu)(yu)額(e)(e)定操作電(dian)壓的(de)85%,并均(jun)不(bu)(bu)得(de)高于(yu)(yu)額(e)(e)定操作電(dian)壓值的(de)110%,以合(he)(he)閘和重合(he)(he)閘的(de)動作可靠性(xing).不(bu)(bu)能滿(man)足上述要求時,應(ying)結合(he)(he)具體情(qing)況予以改進.
斷路(lu)(lu)器操(cao)作時(shi)(shi),如合閘電(dian)源(yuan)電(dian)纜壓(ya)(ya)降(jiang)過大,不能滿(man)足規定的(de)操(cao)作電(dian)壓(ya)(ya)時(shi)(shi),應更換成截面大的(de)電(dian)纜以減少壓(ya)(ya)降(jiang).設計(ji)部門在設計(ji)時(shi)(shi)亦(yi)應考慮電(dian)纜所造成的(de)線路(lu)(lu)壓(ya)(ya)降(jiang).
7.2 220kV及(ji)以(yi)上電(dian)(dian)(dian)(dian)(dian)(dian)壓等級變(bian)電(dian)(dian)(dian)(dian)(dian)(dian)所所用電(dian)(dian)(dian)(dian)(dian)(dian)應有(you)兩路(lu)可(ke)靠電(dian)(dian)(dian)(dian)(dian)(dian)源(yuan).凡(fan)新建變(bian)電(dian)(dian)(dian)(dian)(dian)(dian)所不得采用硅整流合(he)閘電(dian)(dian)(dian)(dian)(dian)(dian)源(yuan)和(he)電(dian)(dian)(dian)(dian)(dian)(dian)容儲能跳閘電(dian)(dian)(dian)(dian)(dian)(dian)源(yuan).對已(yi)運行的(de)電(dian)(dian)(dian)(dian)(dian)(dian)容儲能跳閘電(dian)(dian)(dian)(dian)(dian)(dian)源(yuan),電(dian)(dian)(dian)(dian)(dian)(dian)容器(qi)(qi)質量必(bi)(bi)須合(he)格,電(dian)(dian)(dian)(dian)(dian)(dian)容器(qi)(qi)的(de)組數和(he)容量必(bi)(bi)須滿足幾臺斷(duan)路(lu)器(qi)(qi)同時跳閘的(de)需要,并(bing)應加裝電(dian)(dian)(dian)(dian)(dian)(dian)容器(qi)(qi)熔絲的(de)監視裝置.經常檢查(cha)電(dian)(dian)(dian)(dian)(dian)(dian)容器(qi)(qi)有(you)無漏電(dian)(dian)(dian)(dian)(dian)(dian)現象,如有(you)漏電(dian)(dian)(dian)(dian)(dian)(dian)應及(ji)時更(geng)換(huan),以(yi)保(bao)證故障時斷(duan)路(lu)器(qi)(qi)可(ke)靠跳閘. 信息來自:輸配電(dian)(dian)(dian)(dian)(dian)(dian)設備網
7.3 應定期檢(jian)查直(zhi)流系統各級熔絲配置是(shi)否合(he)理(li),熔絲是(shi)否完(wan)好(hao),操作箱是(shi)否進水受潮,二次(ci)接線是(shi)否牢固,分,合(he)閘線圈有無(wu)燒損.
8 、預防(fang)液(ye)壓(ya)機(ji)構漏油,慢分
8.1 預防(fang)漏油措施:
(1)新裝(zhuang)或檢修斷路器時,應(ying)徹底清洗油(you)箱底部,并對液(ye)壓油(you)用濾(lv)油(you)機過(guo)濾(lv),保證管路,閥(fa)體無滲漏和雜物.
(2)液(ye)壓機(ji)構油泵(beng)啟(qi)動頻(pin)繁或(huo)補壓時間(jian)過長,應(ying)檢查原因并(bing)應(ying)及時停電處理.
(3)處(chu)理(li)(li)儲壓筒活塞(sai)桿漏油時(shi),應同時(shi)檢查處(chu)理(li)(li)微動開(kai)關,以保證微動開(kai)關動作可靠(kao).
8.2 防止失壓后重新打壓慢(man)分
液壓(ya)機(ji)構(gou)發生失壓(ya)故(gu)障時必須及時停電(dian)處理.若斷(duan)路器不能停電(dian)處理,在運行狀態下(xia)搶修時,為防止重新打壓(ya)造成慢分(fen),必須采取以下(xia)措(cuo)施: 信息請登陸:輸配(pei)電(dian)設備網
(1)在失壓閉鎖(suo)后(hou),未采取(qu)防慢(man)分措施前(qian)嚴禁人為(wei)啟(qi)動油泵打壓.
(2)在(zai)使(shi)液壓(ya)(ya)(ya)系統泄壓(ya)(ya)(ya)前(qian)應將卡具裝(zhuang)好,也可將工(gong)作(zuo)缸(gang)與(yu)水平拉桿的連接解脫.嚴禁使(shi)用鐵板,鐵管支撐或鋼絲綁扎.處(chu)理(li)完畢重新打(da)壓(ya)(ya)(ya)到額定壓(ya)(ya)(ya)力后(hou),按(an)動合(he)閘(zha)閥使(shi)其(qi)合(he)閘(zha),如卡具能輕(qing)易(yi)取下或圓(yuan)柱銷(xiao)能輕(qing)易(yi)插入,說(shuo)明故(gu)(gu)障已排除(chu),否(fou)則(ze)仍有故(gu)(gu)障,應繼續修理(li),不(bu)得強行(xing)取下卡具.
(3)應(ying)定(ding)(ding)期檢(jian)查合閘保持彈簧在合閘位(wei)置(zhi)時的拉伸長度,并調整到制造廠規(gui)定(ding)(ding)的數據.對斷路器進(jin)行(xing)檢(jian)查時,應(ying)檢(jian)查合閘位(wei)置(zhi)液壓系(xi)統失壓后,水平(ping)拉桿的位(wei)移是否超過制造廠的規(gui)定(ding)(ding).
9 、預(yu)防斷路器進水受潮
9.1 對(dui)(dui)725kV及以上電壓等(deng)級(ji)少油(you)斷路器在(zai)新裝(zhuang)前(qian)及投(tou)運(yun)一年后應(ying)檢查(cha)(cha)鋁帽上是否(fou)(fou)有砂眼,密封端(duan)面是否(fou)(fou)平(ping)整,應(ying)針對(dui)(dui)不(bu)同(tong)情況分(fen)別處理,如(ru)采取(qu)加裝(zhuang)防雨帽等(deng)措施.在(zai)檢查(cha)(cha)維護時應(ying)注意檢查(cha)(cha)呼(hu)吸孔,防止被油(you)漆等(deng)物堵死.
9.2 為防止液壓機構儲壓缸氮氣室生銹,應使用高純氮(微水含量小于(yu)20L/L)作(zuo)為氣源.
9.3 對斷路(lu)器除定(ding)期進行預防性試驗外(wai),在雨季應增(zeng)加檢查和(he)試驗次數,對油斷路(lu)器應加強對絕緣油的(de)檢測.
9.4 405kV電(dian)壓等(deng)級(ji)多油斷路器電(dian)流互感器引(yin)出(chu)線,限(xian)位(wei)(wei)螺釘,中間聯軸孔堵頭,套(tao)管連接(jie)部位(wei)(wei),防爆(bao)孔及油箱蓋密封用(yong)石(shi)棉繩等(deng)處,均(jun)應密封良好,無損壞變形(xing). 9.5 裝于洞(dong)內的開關設備應保持洞(dong)內通(tong)風和空(kong)氣干燥,以防潮(chao)氣侵入滅(mie)弧室造成(cheng)凝(ning)露.
10 、預防高(gao)壓(ya)開關設備機(ji)械損(sun)傷(shang)
10.1 對于有(you)(you)托架的72~12kV電(dian)壓等級少油斷路器,安裝時其(qi)支持(chi)絕緣子應與(yu)(yu)托架保持(chi)垂直并(bing)固定牢靠,上(shang),下(xia)端連接引線(xian)的連接不(bu)應受過大應力,導電(dian)桿與(yu)(yu)靜(jing)觸(chu)頭應在一個垂直線(xian)上(shang).若發現絕緣子有(you)(you)損傷應及(ji)時更換(huan),并(bing)檢查原因.
10.2 各種瓷件的連接和緊固應對稱(cheng)均勻用(yong)力,防止(zhi)用(yong)力過猛損傷瓷件.
10.3 檢修時應(ying)對開關設備的(de)各連接拐臂,聯板(ban),軸,銷進行(xing)檢查,如發(fa)現彎曲,變形或斷(duan)裂,應(ying)找出原因,更(geng)換零(ling)件并采取預防措施(shi).
10.4 調整開關設備時應用慢分,慢合檢(jian)查(cha)有(you)無(wu)卡澀,各種(zhong)彈(dan)簧和緩沖(chong)裝置應調整和使用在其允許的拉伸(shen)或壓縮限度內,并定期檢(jian)查(cha)有(you)無(wu)變(bian)形(xing)或損壞.
10.5 各(ge)種(zhong)斷路器(qi)的(de)油(you)(you)緩(huan)(huan)沖(chong)(chong)器(qi)應調(diao)整適當(dang).在(zai)(zai)調(diao)試(shi)時,應特別注意檢查油(you)(you)緩(huan)(huan)沖(chong)(chong)器(qi)的(de)緩(huan)(huan)沖(chong)(chong)行程和觸頭彈(dan)跳情況,以(yi)驗證緩(huan)(huan)沖(chong)(chong)器(qi)性(xing)能(neng)是(shi)否(fou)良好,防(fang)止由于(yu)緩(huan)(huan)沖(chong)(chong)器(qi)失(shi)效造成拐臂和傳動機構損壞(huai).禁止在(zai)(zai)緩(huan)(huan)沖(chong)(chong)器(qi)無(wu)油(you)(you)狀態下(xia)進行快速操作.低(di)溫地(di)區使用(yong)的(de)油(you)(you)緩(huan)(huan)沖(chong)(chong)器(qi)應采用(yong)適合低(di)溫環境(jing)條件的(de)緩(huan)(huan)沖(chong)(chong)油(you)(you).
10.6 真空滅(mie)(mie)弧室安(an)裝時,先使靜(jing)觸(chu)頭端(duan)面與靜(jing)觸(chu)頭支(zhi)架連接(jie)(jie)牢(lao)固,再連接(jie)(jie)動(dong)觸(chu)頭端(duan),使動(dong)觸(chu)頭運動(dong)軌跡在滅(mie)(mie)弧室中軸線上,防止(zhi)滅(mie)(mie)弧室受扭力而形成裂紋或漏氣(qi).10.7 126kV及以(yi)上電壓等級(ji)多斷口斷路器,拆一端(duan)滅(mie)(mie)弧室時,另一端(duan)應設法支(zhi)撐.大修時禁止(zhi)爬在瓷柱(zhu)頂部進行(xing)工作,以(yi)免損壞支(zhi)持瓷套(tao).
34>>
10.8 均壓電容器安裝時,防止因"別(bie)勁"引起漏油,發現漏油應予(yu)處理或更換.
10.9 開關設備基礎支架設計應牢固可(ke)(ke)靠(kao),不可(ke)(ke)采用(yong)懸臂梁結(jie)構.
10.10 為防(fang)止機械固定連接部分操作松動,建議采用(yong)厭(yan)氧膠防(fang)松.
10.11 為防止運行中的(de)SF6斷(duan)路(lu)器及GIS絕緣拉桿拉脫事故的(de)發生,應監(jian)視分(fen),合(he)閘(zha)指示器處與(yu)絕緣拉桿相(xiang)(xiang)連的(de)運動(dong)部件相(xiang)(xiang)對(dui)位置有無變化,對(dui)于不(bu)能觀測(ce)其相(xiang)(xiang)對(dui)位置變化的(de)斷(duan)路(lu)器,可定期(qi)作斷(duan)路(lu)器不(bu)同期(qi)及超程測(ce)量,以便及時發現(xian)問題. 11、 預防SF6高壓開關設備漏氣(qi),污染
11.1 新裝或檢修SF6開關設(she)備必須嚴格按照GB,DL/TSF6氣體和氣體絕緣(yuan)金屬封閉開關設(she)備有關技術標準(見附錄(lu))執(zhi)行.
11.2 室內(nei)安(an)裝運行的(de)氣體絕(jue)緣金(jin)屬封閉開(kai)關設備(bei)(簡(jian)稱GIS),宜(yi)設置一定數量的(de)氧量儀(yi)和SF6濃(nong)度報警儀(yi).人員(yuan)進入設備(bei)區(qu)前必須先行通風(feng)15min以上.
11.3 當SF6開關設備(bei)發生泄漏(lou)或爆炸(zha)事故時,工(gong)作人員應按安全防護(hu)規定進行(xing)事故處理.
11.4 運行(xing)中SF6氣體微量(liang)水分或漏(lou)氣率不合格時,應及時處(chu)理,處(chu)理時SF6氣體應予回收,不得隨意向大氣排放(fang)以免(mian)污染(ran)環(huan)境及造成人員中毒事故.
11.5 密度繼電器(qi)及(ji)氣壓表應結合安裝(zhuang),大(da)小修定期校(xiao)驗.
116 SF6開關設備應按有關規定定期進(jin)行(xing)微水含量和泄(xie)漏的檢測.
12、 預(yu)防高壓(ya)開關設備載流導體(ti)過熱12.1 用紅線測溫儀檢(jian)查開關設備的(de)(de)接頭部,特別(bie)在高峰負荷或盛(sheng)夏(xia)季節,要加強(qiang)對(dui)運行設備溫升(sheng)的(de)(de)監(jian)視,發現不合格應(ying)及時處理.
12.2 對開關(guan)設備上(shang)的銅鋁過渡接頭要(yao)定期檢查.
12.3 在交接(jie)(jie)和(he)預防性試驗中(zhong),應嚴(yan)格按照標(biao)準(zhun)和(he)測量方法檢(jian)查(cha)接(jie)(jie)觸(chu)電阻.
13 、預(yu)防高壓開關柜事故
13.1 新(xin)建,擴建和改造(zao)工(gong)程中,宜選(xuan)用(yong)加(jia)強(qiang)絕緣型金屬封(feng)閉式高(gao)壓(ya)開關柜,特別是發(fa)電廠和潮濕污穢地區必須選(xuan)用(yong)加(jia)強(qiang)絕緣型且母線室封(feng)閉的高(gao)壓(ya)開關柜.
13.2 高壓開(kai)關柜中的(de)絕(jue)緣件(如(ru)絕(jue)緣子,套(tao)管,隔(ge)板和觸(chu)頭罩等(deng))嚴禁采(cai)用酚醛樹脂,聚(ju)氯乙烯(xi)及聚(ju)碳酸脂等(deng)有機絕(jue)緣材料(liao),應采(cai)用阻(zu)燃性絕(jue)緣材料(liao)(如(ru)環氧或SMC材料(liao)).
13.3 在開關柜配(pei)電室配(pei)置通(tong)風防潮設備,在梅雨,多雨季節或需(xu)要時啟動(dong),防止凝露(lu)導致絕緣事故.
13.4 進行母(mu)線(xian)和柜間隔(ge)離是防止開(kai)關(guan)柜"火燒(shao)連營"的(de)有效措施.另外(wai),應加強柜內二次(ci)線(xian)的(de)防護,二次(ci)線(xian)宜由阻(zu)燃(ran)型軟管(guan)或金屬軟管(guan)包裹,防止二次(ci)線(xian)損傷.
13.5 對(dui)于老式的五防(fang)功能不完善的固定柜或(huo)手車柜,應完善其五防(fang)功能,避免和減少人身及(ji)設備事故.
14、 預防隔離開關(guan)事故 信(xin)息來源://tede.cn
14.1 堅持隔離開關(guan)定(ding)期大小修(xiu)制度(du) 信(xin)息來自:www.tede.cn
隔(ge)離開(kai)關一般3~5年至少進(jin)行(xing)一次大修(xiu)(xiu),不能按期大修(xiu)(xiu)者應(ying)增加(jia)臨修(xiu)(xiu)次數(shu).126kV電壓等級(ji)及以(yi)上隔(ge)離開(kai)關1~2年至少小修(xiu)(xiu)一次.
14.2 對于久未停電(dian)(dian)檢修(xiu)的母線側隔(ge)離(li)開(kai)關應積(ji)申(shen)請停電(dian)(dian)檢修(xiu)或開(kai)展帶電(dian)(dian)檢修(xiu),防止和減少惡(e)性事故的發生.
14.3 結合(he)電力(li)設備預(yu)防(fang)(fang)性試驗應加(jia)強對隔離開關(guan)(guan)轉動部件,接觸部件,操動機(ji)構,機(ji)械及電氣閉(bi)鎖裝置的(de)檢查與潤(run)滑,并進行操作試驗,防(fang)(fang)止(zhi)機(ji)械卡澀(se),觸頭過熱,絕(jue)緣子斷裂等事故的(de)發生(sheng),隔離開關(guan)(guan)的(de)可靠(kao)運行.
14.4 應對GW5,GW6,GW7型等(deng)問題較多的隔離開(kai)關(guan)傳動(dong)(dong)部件,操(cao)動(dong)(dong)機構和(he)導電回路等(deng)進行完善化(hua)改造.
14.5 新(xin)裝或(huo)檢修隔離開關(guan)應在瓷柱與法蘭(lan)結合面涂(tu)以性能良好的硅類防(fang)水膠. 15、 預防(fang)SN4-(G)型少(shao)油斷路(lu)器事故(gu) 信息來源://www.tede.cn
15.1 該型斷路(lu)器額定短路(lu)開(kai)斷和關合電流均遠低于其銘牌參數(shu),運行中(zhong)實際短路(lu)開(kai)斷電流不(bu)應超過58kA(有效(xiao)值),關合電流不(bu)應超過60kA(峰(feng)值).
15.2 不允許(xu)使用自動(dong)重合閘操作,短(duan)路跳(tiao)閘后不允許(xu)強送.
15.3 定期對瓷套或支持絕緣子(zi)進行清洗,特別是底部的支持絕緣子(zi)不能有油漬和臟污現象.
15.4 尚使用(yong)該型斷路器的單(dan)位應盡快安排更換.
34

地址:山(shan)東省德州市齊河(he)縣(xian)經(jing)濟開(kai)發區向陽(yang)北路6號